What Kept My Heat Pump Running Nonstop in Garner?
Garner · July 2026 · Mario · From our service records
What the customer reported
The property manager for an apartment in Garner reported HVAC issues, with the main problem described as a contactor that couldn't release and a volt issue.
What we found and did
Mario found the heat pump's contactor engaged despite no active call for cooling, and the capacitor was faulty with a reading of zero. He replaced both the capacitor and the contactor to restore the proper electrical components. Continuing the diagnostic at the air handler, he discovered that the 24V signal for the Y terminal was not reaching the heat pump due to a wiring fault, and he corrected the wiring.
Result
After Mario thoroughly tested communication between the thermostat, air handler, and condenser, the unit was cooling properly and functioning according to manufacturer specifications.