AC Not Cooling After Freezing Over in Greensboro
Greensboro · November 2026 · Bernard & Autumn · From our service records
What the customer reported
A Greensboro homeowner in the 27405 area reported that the system was not cooling and that the unit had previously frozen over.
What we found and did
Autumn found R-410A refrigerant pressures below expected operating levels, and the fuses in the outdoor disconnect exceeded the manufacturer's specified maximum overcurrent protection rating. She replaced them with correctly rated fuses, added refrigerant leak sealant, and charged the system with an additional 3 lbs of R-410A. Other visits on this job turned up an active yellow jacket nest inside the disconnect enclosure, which had to be removed before diagnostics could continue. A later inspection found fire damage to the high-voltage wiring, portions of the low-voltage wiring, and multiple furnace components, so a quote was to be provided for replacing the affected electrical components.