Apartment AC Units Failing Before Move-In Day in Durham
Durham · September 2026 · Mario, Travis, Dexter & Jeorell · From our service records

What the customer reported
A property manager at a Durham apartment community in the 27707 area reported several units that were not cooling properly, including one that was cooling but had high levels of humidity, and requested same-day emergency service because residents were moving in.
What we found and did
Over six visits, the team diagnosed several separate problems. Mario found one compressor failed/burned out and drawing zero amperage while the capacitor and contactor tested within acceptable parameters, and because that system was over 15 years old and used R-22 refrigerant, he strongly recommended complete system replacement over a compressor repair. Travis found that a system installed in 2024 had a return plenum that was not properly sealed and noted the outdoor unit was listed as 2T with a 1.5T indoor unit, so a quote was prepared to evaluate and reseal the return and supply plenums. The team also found one unit completely out of Freon with a compressor that had taken a toll from running without it, and another unit with somewhat abnormal refrigerant pressures and two filter-driers installed back-to-back in the suction line.
Result
On the unit that was up and running, the space temperature pulled down approximately 2 degrees after the thermostat was turned on, confirming it was providing cooling.