Water Pooling From Upstairs AC Drain in Rolesville
Rolesville · August 2026 · Manny & Jeorell · From our service records

What the customer reported
The homeowner noted water pooling from the upstairs drain and asked about a reroute.
What we found and did
Testing showed two failing 35/5 µF dual-run capacitors: the upstairs herm terminal was weak at 32.79 µF (min 32.9 µF) and the downstairs fan terminal was weak at 4.44 µF (min 4.7 µF). Manny and Jeorell rinsed the outdoor coils on both systems, flushed the drain lines, added pan tablets, verified electrical connections, and tested refrigerant levels. The capacitor replacements and a re-pipe of the 2nd-floor condensate line for proper pitch and drainage were recommended, along with a 1-year maintenance agreement.
Result
Both systems confirmed proper temperature splits of 15°F upstairs and 14°F downstairs.